■ 8-channel parallel output of withstand voltage,
and each channel is non-interfering
■ Output: AC: 5kV/10mA; DC: 6kV/5mA
■ Insulation resistance test voltage: 0.10kV -1.00kV
■ Each channel can be extended with four-channel scanners,
support 4 four-channel scanners at most which means one
instrument can be extended to 128 channels
■ Four-channel scanner supports contact check function
■ 7-inch 800×480 dot-matrix, TFT-LCD display
■ Chinese and English operation interface and concise
interface operation design
■ Enhanced security: electric shock protection
■ Rapid discharge and arc detection function
■ Arbitrarily set voltage rising time and test time in 999.9
seconds; freely set waiting time for insulation resistance
■ Key-Lock Function
■ Display the PASS/FAIL result of each channel independently
and the total result simultaneously
■ Store 100 test files and each file can hold at most 20 testing
steps
■ Automated test system
■ Household appliances
■ Transformers, motors
■ Electrical equipment
■ Lighting industry
■ New energy vehicles
■ Electronic components
■ Medical equipment
Model | TH9010 | TH9010A | |
Number of Units | separate channel | separate channel | |
Withstanding Voltage Test | |||
Output Voltage | AC | 0.10kV — 5.00kV ±2% | |
DC | 0.10kV — 6.00kV ±2% | ||
Current TestRange | AC | 0mA — 10.00mA ±(2% readings + 5 digits) | |
DC | 0uA — 5.00mA ±(2% readings + 5 digits) | ||
Rapid Discharge Function | Discharge after test ends (DCW) | ||
Insulation Resistance Test | |||
Output Voltage | 0.10kV — 1.00kV ±2% | ||
Resistance Test Range | 0.1MΩ — 10.0GΩ | ||
Resistance Test Accuracy | 0.10MΩ — 999MΩ ±10%1.00GΩ — 10.0GΩ ±20% | ||
Discharge Function | Discharge after test ends | ||
Arc Detection | |||
Test Range | Corresponding Current | 1mA — 20mA | |
General Specification | |||
Voltage Rising Time | 0.1s — 999.9s | ||
Test time Setting (AC/DC) | 0.2s — 999.9s | ||
Voltage Fall Time | 0.1s — 999.9s | ||
Waiting Time (IR) | 0.2s — 999.9s | ||
Time Accuracy | ±(1%+0.1s) | ||
Memory | Store 100 test files and each file can hold at most 20 testing steps | ||
Interface | |||
Standard | HANDLER, RS232, USB DRV, USB HOST |
Optional | |||||
Accessories name | Model |